Total 3D Linearisation
Whether it be pressure, flow, level, density or interface, applications with gases, liquids or steam: differential pressure (DP) measurement technology is suitable for nearly all processes while covering an extreme range of process temperatures and pressures.

Innovative measuring cell
There are three influence factors on the measurement uncertainty of DP transmitters:
Linearity of the differential pressure (DP)
Ambient temperature effect (T)
Line/static pressure effects (SP)
These influences can be caused by changing process conditions, and may result in inaccurate readings delivered to process control by the DP transmitter.
To overcome this, KROHNE has new innovative approach on the DP measuring cell design. The DP cell itself has extremely small dimensions and thus a low weight. The reduction of unnecessary material assures fast reaction on ambient temperature changes. The small dimensions reduce the amount of fill fluid volume to assure the lowest possible ambient temperature effects . The small diaphragm footprint grants a small area force at even highest static pressure ranges of 400 bar/ 5,800 psi or 700bar/ 10,000 psi. In sum, the measuring cell design combines high performance and reliability with a small installation footprint.
The KROHNE Total 3D linearization starts with running a full raw data acquisition to measure the uncertainty against a known reference on a minimum of 400 discrete measurement points.
Every DP cell passes through its entire specified operational range – for example :
Differential pressure range P: -500 … +500 mbar*
Ambient Temperature range: -40…+85 °C / -40…185 °F
Static line pressure: 0…160 bar / 0…2320 psi
The result is a three-dimensional (“3D”) matrix of individual linearization coefficients for each measuring cell. They are put in a correction polynomial and are uploaded to the measuring cell front-end electronics. After this raw data acquisition run, a final calibration run is performed to confirm that each individual dp-cell complies with KROHNEs stringent 3-sigma performance specifications.
After passing the Total 3D linearisation, the measuring cells are assembled to an OPTIBAR DP transmitter. All relevant parts are marked by data matrix code so that all production and calibration data can be traced back for each individual transmitter.